Description
Product Details:
Brand Name: SAFESAVE
Model Number: SJR3-3000 Series
Rated power: 9kw-115kw
Type: 3-phase
Power supply: 220VAC
Inbuilt bypass: Yes
Communication port: RS485
Protective class: IP20
Storage temperature: -25℃~70℃
Application: Blender/Crusher/Pulping machine
Warranty: 18 months
Video of SJR3-3000 series soft starter
Product Overview:
The SJR3-3000 series has a built-in bypass motor soft start and integrated bypass contactor, which greatly reduces the construction cost of the application. It is different from the installation and wiring maintenance of the external soft start. It is also different from the high heat conflict of the thyristor online soft start. This series also supports the bus function of Modbus protocol to support large-scale industrial control layout.
Product Features:
1. Anti shock: Accorded with IEC68-2-27: 15g, 11ms
2. Seismic capacity: Vibration intensity is 0. 5G or less at an altitude less than 3000 meters.
3. Ambient temperature: The capacity needn't be reduced when the working temperature is between 0℃ C and 40℃ ( At the temperature between 40℃ and 60℃, the current should be decreased 2% whenever the temperature is 1℃ higher. )
4. Storage temperature: -25℃~70℃
The list of rated power for SJR3-3000 series softstarter
Dimensions:
Application:
Certificate:
About Us
With years of efforts, Saikong has developed more than 100 models of 10 series of products by our outstanding talents and technology. Our R&D center has an experienced research and development team, working closely with Scientific Research Departments of the Institute of Mechanical and Electrical Engineering and Automation of Shanghai University, the Science and Technology Institute, and Information Technology Department of Fudan University. Our products have been applied to some big projects such as BMDA Intelligent Irrigation System, Shanghai World Expo, Beijing Olympic stadiums, South–to-North Water Division Project, Pudong international airport.
Technical specification of SSR series softstarter | |
Frequency | 50/60Hz±5Hz |
Rated main voltage | 220-500±10%VAC(chose by customer); 400VAC±10%(acquiescent) |
Control source voltage | 100-240VAC-15%+10% or 24VDC(chose by customer); 100-240VAC±10%(acquiescent) |
The motor adapted | Three-phase squirrel-cage induction motor |
Times of start per hour | <5 at 400% FLA |
Motor rated operational current | Motor full load current: 1.5-75A |
Initial voltage | 30%-70%Un |
Start slope | 1-30 seconds |
Stop slope | 1-30 seconds |
Over current | During start,operation,stop,output current over limit |
Unbalanced current | Output current unbalanced level beyond the setting |
1²t over load | May set to 10A,10...overload protection base on the setting to delay protection stop |
Missing phase/No voltage | Stop the softstarter when 1 or 2 phases failed or no voltage input |
Thyristor(SCR) overtemp | Stop the softstarter when the radiator temperature rises above 80℃ |
Phase sequence | Forbid starting when the input phase sequence is wrong (If the function is unnecessary, please tell us before ordering) |