220v Single Phase Soft Starter

Description

Product Details:
Brand Name: SAFESAVE
Model Number: SSR22-A-1P1
Input/Output power: 0.37kW~5.5kW
Input/Output voltage: 220v single phase
Built-in bypass: Yes
Packing Dimension: 19*10.5*11cm
G. W: 1kg
Frequency: 50/60Hz
Warranty: 18 months

Share:

Product Details

Technical Parameter

SSR SOFTSTARTER.jpg



Product Overview:

SSR series soft starter are all digital motor soft start products, It may control the motor started and stopped on a smooth speed changing, It also offers the best protections to motor and itself. It is the better substitute control method to the traditional A-Y motor start and auto transformer start Control.


Product Functions:

◆ Built-in bypass

◆ Multiple protections

◆ Spacing saving

◆ Three/Single phase control

◆ Optional communication

◆ Easy control



ac motor softstarter.jpg





Internal Analytic Diagram soft starter.jpg



motor soft starter.jpg

 

 


 

 

Internal Control Diagram:

 

1.png

 

 

 

 

 

Soft Starter Wiring Mode:


2.png

 

 

 

 

Application Diagram

 

SSR.png



Control power supply and control input:

When using 100-240VAC as a control power,

①Connect AC power line, ②Connect AC power neutral;

Join the contact K between①and③,

Soft starter runs when K closed, soft starter stops when K disconnected; If the control input cable too long or unseparated wiring with power supply, cause input signal with "Induced voltage" Please add a relay at the input, so as to avoid the"induced voltage " which leads to malfunction or damage of the soft starter.

5.1

When using 24VDC as control power,

①Connect to DC+, ②connect to DC-;

Join the contact K between①and③,

Soft starter runs when K closed, Soft starter stops when

K disconnected; If the control input cable too long or

unseparated wiring with power supply, cause input signal with "induced voltage" Please add a relay at the input, so as to avoid the "induced voltage" which leads to malfunction or damage of the soft starter.

6.1

◆Caution:

The control power supply voltage must be matched the products, otherwise the input of the control voltage will exceed the range, which will lead to soft starter damage.

When the control power supply is DC power, the positive and negative pole must be connected to the correct terminal.

◆Relay output

④,⑤ terminal for running relay output.

When SLR soft starter is on running (start/ bypass/ soft stop),

K1 closes. ⑥⑦ terminal is fault relay output, When the SLR soft starter detects a fault K2 closes. K1, K2 contact capacity 220VAC 5A

7.1

◆Caution:

In order to use the SSR soft starter safely, The fault relay K2 should be connected in the circuit of the control(release )of the circuit breaker between the power source and the SLR main power terminal. When he soft starter detects the fault, the K2 action can disconnect the power breaker at the same time.


Technical specification of SSR series softstarter
Frequency 50/60Hz±5Hz
Rated main voltage 220-500±10%VAC(chose by customer);
400VAC±10%(acquiescent)
Control source voltage 100-240VAC-15%+10% or 24VDC(chose by customer);
100-240VAC±10%(acquiescent)
The motor adapted Three-phase squirrel-cage induction motor
Times of start per hour <5 at 400% FLA
Motor rated operational currentMotor full load current: 1.5-75A
Initial voltage 30%-70%Un
Start slope1-30 seconds
Stop slope1-30 seconds
Over current During start,operation,stop,output current over limit
Unbalanced currentOutput current unbalanced level beyond the setting
1²t over load May set to 10A,10...overload protection base on the setting
to delay protection stop 
Missing phase/No voltage Stop the softstarter when 1 or 2 phases failed or no voltage input 
Thyristor(SCR) overtempStop the softstarter when the radiator temperature rises above 80℃
Phase sequenceForbid starting when the input phase sequence is wrong
(If the function is unnecessary, please tell us before ordering)